Fire Alarm Panel - 4 Zone Fire Control Panel - ESP Fireline MAG4P - ABS Case Fireline Protection - Conventional fire warning system The MAG Fire Alarm Centre has been carefully designed to answer the rigorous demands of specifiers, installers and users. For specifiers, the MAG Alarm Centre offers a host of features, designed into a quality engineered package. For installers, the MAG range is simplicity itself to install, program and expand. For users, the MAG Alarm Centre's confusion free instructions are clear and easy to understand and follow. Quality Reliability and Performance are the key words synonymous with the MAG Alarm Centre range. Features: 4 programmable zones Active end of line monitoring and head removal 30 fire detectors per zone Unlimited number of call points per zone Integral evacuate alarm button Enable/disable security key One man walk test facility Volt free fire change over relay Individual sounder circuit fault ID Specifications: Inputs: Max detectors per zone = 30 Power: Mains fail consumption = 50mA Mains supply = 230 VAC ± 10% Standby supply = 1 x 7ah 12V S.L.A. Battery Power availability = 0.7 amps Outputs: Sounder 1 = 24V (max 300mA fused) Sounder 2 = 24V (max 300mA fused) Fault/fire relay = Volt free 500mA @ 24V (max load) Auxiliary output = 24VDC (300mA fused) Enviroment: Working Temperature = 0 to 40 OC Humidity = 0 - 95% Dimensions (mm) = 340W 290H 100D